Parameter 418 [Brake TP Sel] selects a value to monitor for diagnostics of the
dynamic brake protection. Possible selections for parameter 418 [Brake TP Sel]
are:

Parameter 419 [Brake TP Data] displays the data selected in parameter 418
[Brake TP Sel].

Cable, Control

See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication

DRIVES-IN001

, for detailed information.

Cable, Motor Lengths

See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication

DRIVES-IN001

, for detailed information.

Cable, Power

See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication

DRIVES-IN001

, for detailed information.

Cable Trays and Conduit

See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives, publication

DRIVES-IN001

, for detailed information.

Parameter 418 [Brake TP Sel]
Setting

Description

0 - “Zero”

Do not monitor any test point for the brake protection.

1 - “Duty Cycle”

Actual duty cycle of the dynamic brake IGBT where a value of 0 in parameter 419
[Brake TP Data] = full open and 1 = full on.

2 - “Power Actual”

Actual power applied to the resistor (Watts).

3 - “Max BodyTemp”

Maximum temperature that the resistor body can handle (°C).

4 - “Max ElemTemp Act”

Maximum temperature that the resistor element can handle (°C).

5 - “BodyTemp Act”

Predicted temperature of the resistor body (°C).

6 - “ElemTemp Act”

Predicted temperature of the resistor element (°C).

7 - “BTmpTrip Stat”

Maximum resistor body temperature has been exceeded when parameter 419
[Brake TP Data] = 1.

8 - “ETmpTripStat”

Maximum resistor element temperature has been exceeded when parameter 419
[Brake TP Data] = 1.

9 - “Int DB Ohms”

Rating of internal resistor when internal resistor is installed (Ohms).

10 - “Data State”

A value of 0 in parameter 419 [Brake TP Data] = initial state, 1 = internal resistor
data loaded, 2 = external resistor data loaded.

11 - “MC BrakeEnbl”

A value of 0 in parameter 419 [Brake TP Data] = dynamic braking disabled, 1 =
dynamic braking enabled.

12 - “1/rdb”

Inverse of the resistance (1/Ohms).

13 - “1/th_eb”

Inverse of the thermal impedance from the resistor element to body (Watts/°C).

14 - “1/ce”

Inverse of the resistor element thermal mass (°C/W*s).

15 - “tamax”

Maximum ambient temperature of resistor (°C).

16 - “1/th_ba”

Inverse of the thermal impedance from the resistor body to element (Watts/°C).

17 - “1/cb”

Inverse of the resistor body thermal mass (°C/W*s).

18 - “DB IGBT Amp”

IGBT current rating (Amps).