To setup the PowerFlex 700S drive to follow a speed reference from the 20-
COMM-C, parameter 691 [DPI Ref Select] must be set to “Port 5.” Parameter
16 [Speed Ref Sel] must be set to “Speed Ref DPI.”

Reference and Feedback values are floating-point values in the PowerFlex 700S.
Use the following logic to transmit and receive reference and feedback data as
unsigned integer data.

Reference to 700S

(Commanded RPM

Base Motor Speed)

32767

------------------------------------------------------------------------------------------------------

=

MOV

CPT

MOV

Speed Reference Via ControlNet to a PowerFlex 700S using a 20-COMM-C module.

The first move instruction is only for visual indication of the speed reference.

Move
Source

CNet_Ref_RPM

1200.0

Dest

CNet_Ref_RPM

1200.0

Compute
Dest

CNet_700S_Ref_Float

22114.959

Expression

(CNet_Ref_RPM/Motor_Base_Speed)*Speed_Conversion_Constant

Move
Source

CNet_Ref_Float

22114.959

Dest

PowerFlex700S_02:0.Data(1)

22115

Feedback RPM

(700S Feedback

32767)

Base Motor Speed

×

=

CPT

MOV

Convert Speed Feedback from 700S via 20-COMM-C

Feedback is returned as a 0 to 32767 number for 0 to Base Speed

Compute
Dest

CNet_700S_Fdbk

1897

Expression

(CNet_700S_Fdbk_Float/Speed_Conversion_Constant)*Motor_Base_Speed

Move
Source

PowerFlex700S_02:1.Data[2]

22114.959

Dest

CNet_700S_Fdbk_Float

34969.0