Droop, Speed regulator output limits, Speed regulator output filter – Rockwell Automation 20D PowerFlex 700S with Phase I Control Reference Manual User Manual

Page 126

Advertising
background image

126

Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Droop

Droop is used to “shed” load and is usually used when a soft coupling of two
motors is present in an application. For more information on droop, see the
section titled “Droop”.

Speed Regulator Output Limits

The outputs from the proportional block and integrator block are summed
together, creating a torque reference. This torque reference is limited by
parameter 102 [Spd Reg Pos Lim] and 103 [Spd Reg Neg Lim].

Speed Regulator Output Filter

Now the torque reference goes through a lead/lag filter, tuned by parameter 95
[SregOut FiltGain] and 96 [Sreg Out Filt BW]. For more information on lead/
lag filters refer to Lead-Lag Filter on page

56

.

Parameter 157 [Logic Ctrl State] bit 8 - “Spd Reg En” indicates when the speed
regulator is enabled. When “Spd Reg En” is on, this allows the speed regulator
output to pass to the torque control loop.

Parameter 302 [Spd Reg PI Out] contains the filtered, limited torque reference
that was generated by the speed regulator.

+

102

103

Limit

Spd Reg Pos Lim

Spd Reg Neg Lim

Output from

Proportional Block

Output from

Integrator Block

95

96

157

08

0

302

0

1

SRegOut FiltGain

SReg Out Filt BW

Logic Ctrl State

(Spd Reg En)

Spd Reg PI Out

to Torque Control

[4A1]

Lead Lag

(kn * s)+ wn

s + wn