Rockwell Automation Publication PFLEX-RM002D-EN-E - August 2013

Chapter 1

Detail Drive Configuration and Operation

Analog Output Configuration

The analog outputs can be linked to either an integer parameter or a real
parameter. Use [Anlg Outx Real] when you are linking to a real parameter and
use [Anlg Outx Integer] when you are linking to an integer parameter.

[Anlg Outx Offset] is added to [Anlg Outx Real] or [Anlg Outx Integer] before
the scaling and limiting blocks. [Anlg Outx Offset] has a range of +/-20V.

The result of [Anlg Outx Offset] plus [Anlg Outx Real] or [Anlg Outx Integer]
is limited by 10 times the value of [Anlg Outx Scale].

Then that limited value is divided by the value of [Anlg Outx Scale].

[Anlg Outx Zero] is added after the scaling and limiting of the analog output
value. [Anlg Outx Zero] can be used to null out any offset from the D/A
converter.

Example Configuration 1:

This configuration sends the motor torque current reference value to a 0-10V
analog output signal.

[Anlg Out1 Real] is linked to [Mtr TrqCurr Ref ]

[Anlg Out1 Scale] = 0.1 per Volt

TB1-B5

TB1-B6

-

+

816

X

Anlg Out1 Volts

818

812

814

815

817

+

Anlg Out1 Zero

Anlg Out1 Offset

Anlg Out1 Integer

Anlg Out1 Real

Anlg Out1 Scale

D/A
12bit

1

[x]

Limit

+

10 [x]

TB1-B5

TB1-B6

-

+

816

X

Anlg Out1 Volts

823

813

819

820

822

+

Anlg Out1 Zero

Anlg Out2 Offset

Anlg Out2 Integer

Anlg Out2 Real

Anlg Out2 Scale

D/A
12bit

1

[x]

Limit

+

10 [x]

TB1-B4

Shield