Setting the Strobe Output Time

The period of time for the strobe output to turn ON (one-shot output time) can be set.

The pulse width can be selected from the following four types.

Setting procedure of the pulse width of the strobe signal

1

Hold down the

key, and select "

oPt on

" with the

key.

Set the common settings.

2

Press the

key, and select function

"

E

" with the

key.

The pulse width of the strobe signal is set.

3

Press the

key, and select

"

E-2

" with the

key.

Set the pulse width to “10” ms.

4

Press the

key to register the setting. Press the

key to return to the measurement state.

If the Measurement Mode is set to normal, the strobe signal is output for the specified
period only when the measurement value is held. If the measurement value is not held, the
strobe signal is output for half the period of sampling cycle.

Function No.

Function (Strobe output time)

E-0

2

2 ms

E-1

5

5 ms

E-2

10

10 ms

E-3

20

20 ms

Refer to "Timing Chart" (4-13 page) for the timing chart.

Refer to "Binary output" (4-16 page) for details of binary output.

OUT1

HI

GO

LO

HI

GO

LO

TIM

OUT2

TIM

OUT1

HI

GO

LO

HI

GO

LO

TIM

OUT2

TIM

OUT1

HI

GO

LO

HI

GO

LO

TIM

OUT2

TIM

Note