5

LK-G-M-NO0-E

LK-G3001PV/LK-G3001P (PNP type)
24 VDC (-) and COM IN are common via a choke coil. Also, COM IN of the expansion
connector is common via a choke coil.

Common for all types
24 VDC (-), SG (GND) of USB, and SG (GND) of RS-232C are all common via a choke coil.
Make sure that a voltage potential difference does not occur with external devices such as
computers or PLC. If a voltage potential difference occurs, use the unit with insulation on
the LK-G power supply and the I/O terminals other than RS-232C and USB.

Precautions for a Positive Grounding Environment

When using a positive grounding environment, watch out for shorts through the COM
terminal.

LK-G3001V/LK-G3001 (NPN type)

LK-G3001P(V)

LK-G3001P(V)

COM OUT

COM IN

DC24V(+)

DC24V(-)

DC24V

COM OUT

COM IN

DC24V(+)

DC24V(-)

DC24V

The power supply (24 VDC) shorts via the
COM terminals, causing malfunctions.

The power supply (24 VDC) shorts via the
COM terminals, causing malfunctions.

LK-G3001(V)

LK-G3001(V)

COM OUT

COM IN

DC24V(+)

DC24V(-)

DC24V

COM OUT

COM IN

DC24V(+)

DC24V(-)

DC24V

GND