4 (config:) masks, 1 (config: masks) ( modem alarm mask, 2 (config: masks) ( switch alarm mask – Comtech EF Data CRS-311 User Manual

Page 119: 3 (config: masks) ( audio mask, 1 (config: masks) æ modem alarm mask, 2 (config: masks) æ switch alarm mask, 3 (config: masks) æ audio mask

Advertising
background image

CRS-311 1:1 Redundancy Switch

Revision 7

Front Panel Operation

MN/CRS311.IOM

5–9

Restore Holdoff is the length of time that the originally faulted modem must stay unfaulted before 
the Switch will automatically put it back online. Both holdoffs can be set from 1 to 99 seconds. 

5.2.2.4 (CONFIG:) MASKS

ALARM MASK: MODEM-ALARMS
SW-ALARMS AUDIO (ENTER)

 
The Switch logs and reacts to both its switch faults and modem faults. Mask either type of fault using 
this submenu. In addition, use this submenu to enable a buzzer as an audible indicator. 

5.2.2.4.1

(CONFIG: MASKS)

Æ MODEM ALARM MASK

MODEM ALARM MASK: NONE
TX RX (ENTER)

 
Select TX or RX to mask the pertinent traffic faults from being reacted to by the Switch. This not 
only prevents the Switch from performing Auto Mode functions when these modem faults are 
sensed, but also keeps the faults from being logged by the Switch.  
 
Note that these selections are global to all the modems. If masking of individual modem faults is 
desired, it should be done directly on the modem. Unmasked modem faults are logged on active 
modems only. 

5.2.2.4.2

(CONFIG: MASKS)

Æ SWITCH ALARM MASK

SWITCH ALARM MASK: NONE

ÉPSU-A ËPSU-B (ENTER)

 
Select which, if either, of the plug‐in power supply units should be ignored in case any of their 
voltage outputs are monitored by the Switch as being out of range. Press ENTER when done. 
 
You can mask only one unit at a time. Normally this is done if you choose to run with only one 
supply, or if a bad supply has been removed for service or replacement. 

5.2.2.4.3

(CONFIG: MASKS)

Æ AUDIO MASK

AUDIO MASK: NONE SW-ALMS
MODEM-ALMS BOTH (ENT)

 
For all Switch or modem  alarms that are unmasked, you may select which alarm types should 
force the Switch to react with an audible buzzer located behind the front panel. In addition, a 
relay  closure  to  ground  activates  on  pin  20  of  the  System  Alarms  connector  so  that  you  may 
attach other indicators. 
 