3) wire size (ul standard), For three-phase, 200v – Yaskawa Sigma-5 Series User Manual:: For Use with Large-Capacity Models-Setup. Rotary Motors User Manual

Page 75

Advertising
background image

3.4 Main Circuit Wiring

3-27

Wiring and Connection

(3) Wire Size (UL Standard)

To comply with the UL standard, use the recommended wires.
The following table shows the wire sizes (AWG) at a rating of 75

°C.

„

For Three-phase, 200V

Combination of

SERVOPACK and

Converter

*

Terminal

Symbols

Screw Size

for

Terminals

Tightening

Torque

(Nxm)

Wire Size

AWG

SGDV-121H

SGDV-

COA2BAA

SERVOPACK

P, N

M8

15.0

Bus bar

attached to

the converter

U, V, W

M8

3.0

1/0

DU, DV, DW

M6

3.0

10

M8

9.0 to 11.0

1/0

Converter

P, N

M8

3.0

Bus bar

attached to

the converter

L1, L2, L3

M8

3.0

1/0

1, 2

M8

3.0 1/0

CN101

(L1C, L2C)

(Connector)

14

B1, B2

M8

3.0

6

M8

9.0 to 11.0

1/0

SGDV-161H

SGDV-

COA3GAA

SERVOPACK

P, N

M8

15.0

Bus bar

attached to

the converter

U, V, W

M8

3.0

3/0

DU, DV, DW

M6

3.0

10

M8

9.0 to 11.0

3/0

Converter

P, N

M10

12 to 20

Bus bar

attached to

the converter

L1, L2, L3

M10

12 to 20

3/0

1, 2

M10

12 to 20

3/0

CN101

(L1C, L2C)

(Connector)

14

B1, B2

M10

12 to 20

4

M8

9.0 to 11.0

3/0