3 Wiring and Connection

3.6.3 Installation Standards

3-44

• If the coil current of NC dynamic brake contactors is 300 mA or higher, obtain an

NO relay that can switch the contactor coil current and voltage and a power supply
for the contactor coil.

3.6.3 Installation Standards

Observe the following installation standards when you use a Yaskawa dynamic brake
unit. Provide at least 70 mm on each side of the unit and at least 200 mm at both the
top and bottom of the unit to enable fan and natural convection cooling.

Power supply
for contactor
coil

Power supply
for contactor coil

NO relay

DV

DU

DW

SERVOPACK

For I/O

power supply

24V

0V

Dynamic brake resistor

(Auxiliary contacts)

DBON

DB24

Dynamic brake contactor

Main circuit surge
absorption unit

Coil surge
absorption unit

CN115

24V

DB

47

45

CN1

0V

DB

70 min.

70 min.

200 min.

200 min.

Mounting
direction

Up

Units: mm