3 Wiring and Connection

3.5.1 Selecting a Regenerative Resistor Unit

3-38

3.5

Selecting and Connecting a Regenerative Resistor Unit

The SERVOPACKs and converters do not contain a regenerative resistor. Select and
connect a regenerative resistor unit and set the regenerative resistor capacity in Pn600
as described in this section.

Contact your Yaskawa representative or the sales department for the detailed specifi-
cations of the regenerative resistor units.

3.5.1 Selecting a Regenerative Resistor Unit

The regenerative resistor units specified by Yaskawa are listed in the following table.
You must acquire the regenerative resistor units separately. Use it only in one of the
combinations that are given in the following table.

WARNING

• Be sure to connect the regenerative resistor unit correctly. Do not short-circuit

between B1 and B2.

Doing so may result in fire or damage to the regenerative resistor unit, SERVOPACK, or

converter or other devices.

SERVOPACK

Model

SGDV-

Converter

Model

SGDV-COA

Model of

Applicable

Regenerative

Resistor Unit

Resist-

ance

(

Ω)

Specifications

121H

2BAA

JUSP-RA08-E

2.4

Four 0.6-

Ω (600-W) resistors con-

nected in series.

161H

3GAA

JUSP-RA09-E

1.8

Two sets of four 0.9-

Ω (600-W)

resistors connected in series are

connected in parallel.

201H

JUSP-RA11-E

1.6

Eight 0.2-

Ω (600-W) resistors

connected in series.

750J

3ZDA

JUSP-RA13-E

6.7

Three sets of two 10-

Ω (600-W)

resistors connected in series are

connected in parallel.

101J

5EDA

JUSP-RA14-E

5

Four sets of two 10-

Ω (600-W)

resistors connected in series are

connected in parallel.

131J

JUSP-RA16-E

3.8

Four sets of three 5-

Ω (600-W)

resistors connected in series are

connected in parallel.