5.8 Limiting Torque

5-63

5

Ope

rat

ion

5.8.4 Torque Limiting Using an External Torque Limit and Analog Voltage

Reference

This function can be used to combine torque limiting by an external input and by analog voltage reference.

When /P-CL (or /N-CL) is ON, either the torque limit by analog voltage reference or the setting in Pn404 (or
Pn405) will be applied as the torque limit, whichever is smaller.

The following chart shows the external torque limiting using an analog voltage reference.

Note: This function cannot be used during torque control since the torque limit by analog voltage reference is input from

T-REF (CN1-9, 10).

(1) Input Signals

Use the following input signals to limit a torque by external torque limit and analog voltage reference.

Refer to 5.5.1 Basic Settings for Torque Control.

Parameter

Meaning

When Enabled Classification

Pn002

n.

3

When /P-CL or /N-CL is enabled, the T-REF terminal
is used as the external torque limit input.

After restart

Setup

Pn300

+

+

+

-

T-REF

V-REF

/N-CL

/P-CL

Pn101

Pn100

Pn400

T-REF filter time constant

Pn415

Torque limit
value

Speed
reference

Pn404

(/P-CL: ON)

Pn402

Pn405
Reverse external torque limit

(/N-CL: ON)

Pn403

Speed
loop
gain

Speed feedback

Torque
reference

SERVOPACK

Torque reference input gain

Forward
torque
limit

Forward
external
torque limit

Reverse torque limit

Speed
reference input
gain

Speed loop
integral time
constant

(See 5.5.1.)

(See 6.9.2.)

(See 5.3.1.)

(See 5.8.1.)

(See 5.8.1.)

(See 5.8.1.)

(See 5.8.1.)

Analog

Type

Signal Name

Connector

Pin Number

Name

Input

T-REF

CN1-9

Torque reference input

SG

CN1-10

Signal ground for torque reference input

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Limit Value

Input /P-CL

CN1-45
[Factory setting]

ON

Forward external torque limit ON

The smallest value of these set-
tings: the analog voltage refer-
ence limit, Pn402, or Pn404

OFF

Forward external torque limit
OFF

Pn402

Input /N-CL

CN1-46
[Factory setting]

ON

Reverse external torque limit ON

The smallest value of these set-
tings: the analog voltage refer-
ence limit, Pn403, or Pn405

OFF

Reverse external torque limit
OFF

Pn403