10 Troubleshooting

10.1.2 Troubleshooting of Alarms

10-10

A.300:
Regeneration Error

An external regenerative resistor

unit is not connected.

Check the external regenerative

resistor unit connection.

Connect the external regenerative

resistor unit.

The regenerative resistor unit is

incorrectly wired, or is removed

or disconnected.

Check the regenerative resistor unit

connection.

Correctly connect the regenerative

resistor unit.

The connection of the I/O signals

(CN901) between the SERVO-

PACK and converter is faulty.

Check the connection of CN901.

Correctly connect CN901.

A fault occurred in the SERVO-

PACK or converter.

While the main circuit power sup-

ply is OFF, turn the control power

supply OFF and then ON again. If

the alarm still occurs, the SERVO-

PACK or converter may be faulty.

Replace the SERVOPACK or con-

verter.

A.320:
Regenerative

Overload

The power supply voltage

exceeds the specified limit.

Measure the power supply voltage.

Set the power supply voltage within

the specified range.

Insufficient regenerative resis-
tance, regenerative resistor
capacity.
Or, regenerative power has been

continuously flowing back.

Check the operating condition or

the capacity using the capacity

selection Software SigmaJunma-

Size+, etc.

Change the regenerative resistance,

regenerative resistor capacity.

Reconsider the operating conditions

using the capacity selection soft-

ware SigmaJunmaSize+, etc.

Regenerative power continu-

ously flowed back because nega-

tive load was continuously

applied.

Check the load applied to the servo-

motor during operation.

Reconsider the system including

servo, machine, and operating con-

ditions.

The setting of parameter Pn600 is

smaller than the regenerative

resistor's capacity.

Check the regenerative resistor unit

connection and the value of the

Pn600.

Set the Pn600 to a correct value.

The regenerative resistance is too

high.

Check the regenerative resistance.

Change the regenerative resistance

to a correct value or use an external

regenerative resistor of appropriate

capacity.

The connection of the I/O signals

(CN901) between the SERVO-

PACK and converter is faulty.

Check the connection of CN901.

Correctly connect CN901.

A fault occurred in the SERVO-

PACK or converter.

The SERVOPACK or converter

may be faulty. Replace the SERVO-

PACK or converter.

A.330:
Main Circuit Power

Supply Wiring Error
(Detected when the
power to the main circuit
is turned ON.)

The regenerative resistor unit was

disconnected when the power

supply voltage to the SERVO-

PACK and converter was high.

Measure the resistance of the regen-

erative resistor unit using a measur-

ing instrument.

Replace the regenerative resistor

unit.

DC power was supplied.

Check the power supply to see if it

is a AC power supply.

Use an AC power supply.

An regenerative resistor unit is
not connected.

Check the regenerative resistor unit

connection.

Connect the regenerative resistor

unit.

The 1 and 2 terminals of the

converter are open.

Check the 1 and 2 terminals on

the converter.

Correctly connect the 1 and 2

terminals on the converter.

The connection of the I/O signals

(CN901) between the SERVO-

PACK and converter is faulty.

Check the connection of CN901.

Correctly connect CN901.

A fault occurred in the SERVO-

PACK or converter.

The SERVOPACK or converter

may be faulty. Replace the SERVO-

PACK or converter.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions