9 Fully-closed Loop Control

9.1.6 Precautions When Using an External Incremental Encoder by Magnescale

9-12

4

Perform a program JOG opera-
tion.

Items to Check

• Does the fully-closed loop

control operate correctly when
operating the SERVOPACK in

standalone mode?

Perform a program JOG operation
and check that the distance that the
servomotor moved is the same as
the distance that is set in Pn531.
Note: Start from a low speed and

gradually increase the speed.

• Program JOG related param-

eters (Pn530 to Pn536)

SERVOPACK

5

Operate the SERVOPACK and
converter.

Items to Check

• Does the fully-closed loop

control operate correctly

including the host controller?

Input the position reference and

check that the SERVOPACK and
converter operate correctly.
Note: Start from a low speed and

gradually increase the speed.

Host controller

(cont’d)

Procedure

Description

Operation

Parameters Requiring

Settings

Controller