10.1 Alarm Displays

10-19

10

Trou

blesh

ooting

A.CF1:
Feedback Option

Module

Communications Error
(Reception error)

Wiring of cable between serial

converter unit and SERVOPACK
is incorrect or contact is faulty.

Check the external encoder wiring.

Correct the cable wiring.

The specified cable is not used
between serial converter unit and
SERVOPACK.

Confirm the external encoder wir-

ing specifications.

Use the specified cable.

Cable between serial converter
unit and SERVOPACK is too

long.

Measure the length of this cable.

Use 20-m cable max.

Sheath of cable between serial

converter unit and SERVOPACK
is broken.

Check the cable for damage.

Replace the cable.

A.CF2:
Feedback Option

Module

Communications Error
(Timer stop)

Noise interferes with the cable

between serial converter unit and
SERVOPACK.

Correct the wiring around serial
converter unit, e.g., separating I/O
signal line from main circuit cable
or grounding.

A serial converter unit fault
occurred.

Replace the serial converter unit.

A fault occurred in the SERVO-
PACK.

Replace the SERVOPACK.

A.d00:
Position Error

Overflow
(Position error exceeded

the value set in the

excessive position error

alarm level (Pn520).)

The servomotor U, V, and W wir-

ings is faulty.

Check the servomotor main circuit

cable connection.

Confirm that there is no contact

fault in the motor wiring or encoder

wiring.

The frequency of the position ref-

erence pulse is too high.

Reduce the reference pulse fre-

quency, and operate the SERVO-

PACK.

Reduce the position reference pulse

frequency or acceleration of posi-

tion reference. Or, reconsider the

electronic gear ratio.

The acceleration of the position

reference is too high.

Reduce the reference acceleration,

and operate the SERVOPACK.

Apply the smoothing function, such

as using position reference accelera-

tion/deceleration time constant

(Pn216).

Setting of the excessive position

error alarm level (Pn520) is low

against the operating condition.

Check the alarm level (Pn520) to

see if it is set to an appropriate

value.

Set the Pn520 to proper value.

A fault occurred in the SERVO-

PACK.

Turn the power supply OFF and

then ON again. If the alarm still

occurs, the SERVOPACK may be

faulty. Replace the SERVOPACK.

A.d01:
Position Error

Overflow Alarm at

Servo ON

This alarm occurs if the servomo-
tor power is turned ON when the
position error is greater than the
set value of Pn526 while the ser-
vomotor power is OFF.

Check the position error amount

(Un008) while the servomotor

power is OFF.

Set position error to be cleared

while the servomotor power is OFF.
Or, correct the excessive position

error alarm level at servo ON

(Pn526).

A.d02:
Position Error

Overflow Alarm by

Speed Limit at Servo

ON

When the position errors remain
in the error counter, Pn529 limits
the speed if the servomotor power
is ON. If Pn529 limits the speed
in such a state, this alarm occurs
when reference pulses are input
and the number of position errors
exceeds the value set for the
excessive position error alarm
level (Pn520).

Set position error to be cleared

while the servomotor power is OFF.
Or, correct the excessive position

error alarm level (Pn520).
Or, adjust the speed limit level at

servo ON (Pn529).

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions