8.1.1 User settings for Bus Differential

The minimum settings for Bus Differential zones for both Alarm-Only and Trip Relays for
Topology 0 are:

Pickup Setting 1 & Pickup Setting 2

= 30 Amps

Time Delay 1 & Time Delay 2

= BAND 1

Backup Function (For Trip Relay only)

= ENABLED

Backup Time Delta (For Trip Relay only)

= Trip Immediately

NOTE: Although the Pickup is set to 30 Amps, Entellisys automatically enforces a “Zone
Minimum Pickup Setting” for Bus Differential. The “Zone Minimum Pickup Setting” is 20% of the
largest CT rating in the corresponding zone.

Figure 8-3 Reduced Let-Thru Mode settings for Bus Differential Relay