The operands available for this relay are listed alphabetically by operand type in Table 11-2.

Table 11-2 Entellisys FlexLogic operands

OPERAND TYPE

OPERAND SYNTAX

OPERAND DESCRIPTION

ELEMENT:
Breaker Control

BREAKER 1 OPENED

BREAKER 1 CLOSED

BREAKER 1 LOCKED OUT

BREAKER 1 CLOSED SPRING CHRGD

BREAKER 1 PRIMARY CONNECTED

BREAKER 1 PRIMARY DISCONNECTED

BREAKER 1 SECONDARY CONNECTED

Breaker 1 open

Breaker 1 closed

Breaker 1 locked out

Breaker 1 closing spring charged

Breaker 1 primary connected

Breaker 1 primary disconnected

Breaker 1 secondary connected

BREAKER 2…30

Same set of operands as shown for
BREAKER 1

ELEMENT:
Bus Differential

BD ZONE 1 TRIP DPO

BD ZONE 1 ALARM DPO

BD ZONE 1 TRIP PKP

BD ZONE 1 ALARM PKP

BD ZONE 1 TRIP OP

BD ZONE 1 ALARM OP

BD ZONE 1 TRIP BACKUP OP

Bus Differential Zone 1 trip function not in
pickup

Bus Differential Zone 1 alarm function not in
pickup

Bus Differential Zone 1 trip function in
pickup

Bus Differential Zone 1 alarm function in
pickup

Bus Differential Zone 1 trip function has
tripped breakers

Bus Differential Zone 1 alarm activated

Bus Differential Zone 1 trip backup function
has tripped backup breakers

BD ZONE 2…4

Same set of operands as shown for BD
ZONE 1

ELEMENT:
Ground Fault

GROUND FAULT 1 PKP

GROUND FAULT 1 OP

GROUND FAULT 1 DPO

Ground Fault 1 in pickup

Ground Fault 1 tripped breaker or activated
alarm

Ground Fault 1 not in pickup

GROUND FAULT 2…30

Same set of operands as shown for
GROUND FAULT 1

ELEMENT:
High Current

HIGH CURRENT 1 PKP

HIGH CURRENT 1 OP

HIGH CURRENT 1 DPO

High Current 1 in pickup

High Current 1 activated alarm

High Current 1 not in pickup

HIGH CURRENT 2…30

Same set of operands as shown for HIGH
CURRENT 1

ELEMENT:
High Resistance
Ground Fault

HRGF 1 PKP

HRGF 1 OP

HRGF 1 DPO

HRGF 1 in pickup

HRGF 1 activated alarm

HRGF 1 not in pickup

HRGF 2…30

Same set of operands as shown for HRGF 1