Specifications, 1 environmental, 2 type tests – GE Industrial Solutions Entellisys System User Manual User Manual

Page 25: 2 specifications, 1 environmental 2.2 type tests, 2specifications

Advertising
background image

Environmental

25

2

2

Specifications

2.1 Environmental

Storage/shipping temperatures

–40 to 85° C

Operating temperatures

0 to 40° C ambient, indoor use

Humidity

5% to 95%, non-condensing, indoor use

2.2 Type tests

Tests are split into two categories:

• EntelliGuard Messenger Tests – the primary protection control element
• Entellisys System Tests – the complete system

Table 2-1 Type tests

Type

Name

EntelliGuard Messenger
Tests

Entellisys System Tests

EMC/Transient

Harmonic Currents

IEC60947-2 sec.F.4.1.2

EMC/Transient

Current Dips and
Interruptions

IEC60947-2 sec. F.4.2

EMC/Transient

Fast Transient Burst

IEC61000-4-4

ANSI C37.90.1

ANSI C37.90.1

ANSI C62.41

IEC61000-4-4

EMC/Transient

Voltage/Current Surge
Immunity

IEC61000-4-5

IE255-22-5

ANSI C62.41

IEC61000-4-4

EMC/Transient

Electrostatic Discharge
Immunity

IEC60947-2 sec. F.4.3

IEC60255-6

EN61000-4-2

EMC/Transient

1MHz Oscillatory SWC

IEC 60255-22-1

ANSI C37.90.1

ANSI C37.90.1

EM emission

Conducted

FCC part 15, subpart B, Class A

EM emission

Radiated

FCC part 15, subpart B, Class A

RFI

Electromagnetic Field
Immunity

IEC60947-2 sec. F.4.4