GE Industrial Solutions Entellisys System User Manual User Manual

Page 148

Advertising
background image

FlexLogic™

148

11

The characteristics of the different types of operands are listed in Table 11-1.

Table 11-1 FlexLogic operand types

Operand type

State

Example format

Characteristics [Input is ‘1’ (= ON) if...]

Contact Input

On

Contact Input On

Voltage is presently applied to the input
(external contact closed).

Off

Contact Input Off

Voltage is presently not applied to the input
(external contact open).

Contact Output

On

Contact Output On

Voltage exists across the contact.

Off

Contact Output Off Voltage does not exist across the contact.

Element (Analog)

Pickup

LONG TIME 1 PKP

The tested parameter is presently above the
pickup setting of an element, which responds
to rising values, or below the pickup setting
of an element, which responds to falling
values.

Dropout

LONG TIME 1 DPO

This operand is the logical inverse of the
above PKP operand.

Operate

LONG TIME 1 OP

The tested parameter has been above/below
the pickup setting of the element for the
programmed delay time, or has been at logic
1 and is now at logic 0 but the reset timer has
not finished timing.

Fixed

On

On

Logic 1

Off

Off

Logic 0

Virtual Input

On

Virtual Input 1 On

The virtual input is presently in the ON state.

Virtual Output

On

Virtual Output 1 On The virtual output is presently in the set state

(i.e., evaluation of the equation which
produces this virtual output results in a “1”).