Alarms and events

220

A

Alarm Dropout Multi Source GF
Sum Zone 1…2

Alarm only multi source ground fault for
summation zone 1…2 has dropped out of
pickup

Alarm Multi Source GF Sum Zone
1…2

Alarm only multi source ground fault for
summation zone 1…2 has operated and
tripped the breakers

Protection Disabled Invalid Cfg
Multi Src GF

File that contains configuration information
for multi source ground fault is bad or
missing, all multi source ground fault
functions are disabled

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Protection Suspended Zone 1…4
Multi Source GF

Multi source ground fault (trip and alarm
only) for zone 1…4 has been suspended

Examine Sequence of Events for cause. It can
be any one of the following:
• Current on one or more phases exceeded

10X (overcurrent pickup/trip event)

• Messenger at a breaker in the zone is not

communicating (Caution CPU Not Rcv
From Messngr)

• Messenger at a breaker in the zone has

been decommissioned (Attention
Messngr Decommssned Msg Proto Ver,
Attention Messngr Decommssned Dupe
IDs Seqs, or Attention Messngr
Decommssned Dupe Ids)

• A Compartment ID button at a breaker in

the zone has been misconfigured

• At least one of the breakers in the zone

has been put into test mode (Test Mode
Initiated From Test Kit)

Protection Resumed Zone 1…4
Multi Source GF

Multi source ground fault (trip and alarm
only) for zone 1…4 has resumed

Protection Suspended Zone 1…2
Sum Multi Src GF

Multi source ground fault (trip and alarm
only) for summation zone 1…2 has been
suspended

Same as Protection Suspended Zone 1…4
Multi Source GF

Protection Resumed Zone 1…2
Sum Multi Src GF

Multi source ground fault (trip and alarm
only) for summation zone 1…4 has resumed

Invalid Set MSGF Zone1…4 Pkup
Chng Rejctd

Pickup setting for multi source ground fault
for zone 1…4 is too low, change is rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid Set MSGF Zone1…4 Alrm
Pkup Chng Rejctd

Pickup setting for alarm only multi source
ground fault for zone 1…4 is too low, change
is rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid Set MSGF Zone1…4 Pkup
Min Used

Pickup setting for multi source ground fault
for zone 1…4 has been set to the minimum
allowable (current setting is too low)

Check pickup setting for MSGF zone. Value
can be set higher if desired.

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips