Single point functions
78
5
Figure 5-11 High Resistance GF settings
5.2.8.4 Usage
The High Resistance Ground Fault Relay goes into pickup if the ground current is above the
pickup threshold and generates an alarm if the ground current remains above the threshold for
longer than the delay setting.
5.2.8.5 Event logging
The HRGF relay generates the following events:
• Pickup High Resistance GF – when the alarm function enters pickup
• Alarm High Resistance GF – when the alarm function operates
• Drop out High Resistance GF – when the alarm function drops out
To view these events, click Sequence of Events on the Main Menu.