Preventive maintenance

172

12

12.1.6 Percent mechanical life

Entellisys calculates the percentage of mechanical life used on each EntelliGuard circuit
breaker. This percentage is updated every time an EntelliGuard circuit breaker transitions from
closed to open, and is calculated by dividing the total number of operations recorded by the
counter by the number of rated operations. (See Equation 12-2 and Table 12-3.)

Equation 12-2 Percentage of mechanical life calculation

12.1.7 Last circuit breaker operation

Entellisys maintains the date and time of the last operation for each EntelliGuard circuit breaker.
This is defined as any transition from closed to open or from open to closed.

Table 12-3 Number of rated operations for various frame sizes

Frame Size

Operations

Rated

800

12500

1600

4000

2000

4000

3200

1500

4000

1500

5000

1500

Rated

Total

Operations

Operations

/

Life

Mechanical