Alarms and events

222

A

Synch Check 1…6 Dead Source
Operate

Dead source criteria for synch check relay
1…6 have been met

Synch Check 1…6 Dead Source
Drop Out

Dead source criteria for synch check relay
1…6 have been met

Synch Check 1…6 V1 Above
Minimum

Voltage source 1 for synch check relay 1…6 is
above the live source threshold

Synch Check 1…6 V1 Below
Maximum

Voltage source 1 for synch check relay 1…6 is
below the dead source threshold

Synch Check 1…6 V2 Above
Minimum

Voltage source 2 for synch check relay 1…6 is
above the live source threshold

Synch Check 1…6 V2 Below
Maximum

Voltage source 2 for synch check relay 1…6 is
below the dead source threshold

Overcurrent (including GF)

Pickup ST Overcurrent

Short time overcurrent function has entered
pickup

Dropout ST Overcurrent

Short time overcurrent function has dropped
out of pickup

Breaker Trip ST Overcurrent

Breaker tripped due to short time overcurrent
condition

Pickup LT Overcurrent

Long time overcurrent function has entered
pickup

Dropout LT Overcurrent

Long time overcurrent function has dropped
out of pickup

Breaker Trip LT Overcurrent

Breaker tripped due to long time overcurrent
condition

Pickup Ground Fault

Ground fault function has entered pickup

Dropout Ground Fault

Ground fault function has dropped out of
pickup

Breaker Trip Ground Fault

Breaker tripped due to ground fault condition

Alarm Ground Fault

Ground fault alarm has operated

Invalid Setting IOC Change
Rejected

Attempt to enable or disable IOC has been
rejected

The setting entered for IOC enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips