GE Industrial Solutions Entellisys System User Manual User Manual

Page 228

Advertising
background image

Alarms and events

228

A

All Metering and Protection
Disabled

CPU is not performing any metering or
protection, either because it does not have a
valid option string or the firmware download
is invalid

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Invalid PT Rating Volts
Suspended

Programmed PT rating is not valid, no voltage
relays or metering will be done for
Messengers that use that Messenger as a
voltage source

Contact GE Post Sales Service (see

How to

contact us on page 2

).

CPU Synch Clock Calibration OK Periodicity of CPU Synch Clock is within spec

limits

Caution CPU Synch Clock Error
Backup Clock On

CPU cannot use CPU Synch Clock (Synch
Clock is missing or calibration failed) and is
running from the software backup clock

Verify that CPU Synch Clock is present and
powered. If it is, contact GE Post Sales Service
(see

How to contact us on page 2

).

CPU Synch Clock OK

CPU is running from the CPU Synch Clock

CPU Synch Clock Freq Mismatch CPU Synch Clock is interrupting at 50 Hz and

CPU is programmed for 60 Hz, or vice versa

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Waveform Capture Ignored
Check Messngr Status

All Messengers either decommissioned or not
communicating, so no waveform data was
captured

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Waveform Capture Ignored
Buffer Protection On

Waveform buffer is full and write protection
is on, so waveform was not captured.

Clear waveforms, or allow Automatic
Overwrite of waveforms.

Note Ethernet Err Port1 Receive
Invalid Frame

CPU received an invalid frame on Ethernet
port 1 (e.g., invalid MAC address or size,
invalid data size)

Verify that no devices other than the
Messengers and CPU are plugged into the
switch that connects the Messengers and
CPU.

Note Ethernet Err Port1 Receive

CPU detected an error on ethernet port 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send

CPU failed to send an Ethernet packet from
port 1.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send
Restart

CPU restarted Ethernet port 1 transmit-driver. Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send
Queue Full

CPU failed to send an Ethernet packet from
port 1 because Ethernet driver
transmit-buffer is full.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr
Decommssned Msg Proto Ver

Message protocol version sent by Messenger
does not match what is expected, Messenger
decommissioned

Messenger and CPU are incompatible,
contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr
Decommssned Dupe IDs Seqs

Two Messengers with the same ID have been
detected

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr
Decommssned Dupe Ids

Two Messengers with the same ID have been
detected

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips

Advertising