Single point functions

66

5

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage. If the option is enabled, the blocking voltage setting is 10% of the nominal
voltage.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.

Figure 5-6 Settings for Over Frequency Relay

5.2.3.5 Usage

Event logging

The following events are logged for the over frequency relay in the Entellisys HMI:

• Alarm Pickup Over Frequency – Alarm only over frequency relay has entered pickup.
• Alarm Over Frequency – Alarm only over frequency relay has operated.
• Alarm Dropout Over Frequency – Alarm only over frequency relay has dropped out of

pickup.

• Voltage Below Overfreq Alarm Blocking Voltage – The voltage has dropped below the alarm

only over frequency blocking voltage threshold.

• Voltage Above Overfreq Alarm Blocking Voltage – The voltage has exceeded the alarm only

over frequency blocking voltage threshold.

• Pickup Over Frequency – Over frequency relay has entered pickup.
• Breaker Trip Over Frequency – Over frequency relay has operated.