FlexLogic™

164

11

Figure 11-6 FlexLogic equation for Virtual Output 3

5. Repeating the process described for VIRTUAL OUTPUT 3, select the FlexLogic parameters for

Virtual Output 4.

a. Start with parameter 99 as follows:

99: The final output of the equation is VIRTUAL OUTPUT 4 which is parameter
“= Virt Op 4”.

98: The operator preceding the output is Timer 2, which is operand “TIMER 2”.

NOTE: The settings required for the timer are established in

FlexLogic timers on page 158

.

97: The operator preceding Timer 2 is OR #2, a 3-input OR, which is parameter “OR (3)”.

96: The lowest input to OR #2 is operand “Cont Ip H1c On”.

95: The center input to OR #2 is operand “TIMER 1”.

94: The input to Timer 1 is operand “Virt Op 3 On”.

93: The upper input to OR #2 is operand “LATCH (S, R)”.

92: There are two inputs to a latch, and the input immediately preceding the latch reset is
OR #1, a 4-input OR, which is parameter “OR (4)”.

91: The lowest input to OR #1 is operand “Virt Op 3 On”.

90: The input just above the lowest input to OR #1 is operand “XOR (2)”.

89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.

88: The upper input to the XOR is operand “Virt Ip 1 On”.

87: The input just below the upper input to OR #1 is operand “Virt Op 2 On”.

86: The upper input to OR #1 is operand “Virt Op 1 On”.

85: The last parameter is used to set the latch, and is operand “Virt Op 4 On”.

b. Write the parameters in numerical order to now form the equation for VIRTUAL

OUTPUT 4:

[85] Virt Op 4 On

[86] Virt Op 1 On