5 metering accuracy – GE Industrial Solutions Entellisys System User Manual User Manual

Page 34

Advertising
background image

Metering

34

4

4.5 Metering accuracy

Table 4-2 shows the metering accuracy for Wh, varh, VAh, W, var, and VA under the following
conditions:

• Nominal frequency
• Nominal voltage
• Power factor of 0.85 to 1.00 for Wh and VAh
• Power factor of 0.00 to 0.15 for varh

Table 4-3 shows the voltage accuracy at nominal frequency:

Table 4-4 shows the current accuracy at nominal frequency:

Table 4-2 Metering accuracy for Wh, varh, VAh, W, var, and VA

Current (percent of nominal CT rating)

Accuracy (percent of reading, includes
current and voltage sensors)

10%

± 5.0%

30%

± 4.5%

50%

± 4.0%

75%

± 3.0%

85-100%

± 2.0%

Table 4-3 Voltage accuracy at nominal frequency

Current (percent of nominal PT rating)

Accuracy (percent of reading, includes
voltage sensors)

50%

± 2.0%

75%

± 1.5%

85-100%

± 0.8%

Table 4-4 Current accuracy at nominal frequency

Current (percent of nominal CT rating)

Accuracy (percent of reading, includes
current sensors)

10%

± 3.5%

30%

± 3.25%

50%

± 2.75%

75%

± 1.75%

85-100%

± 0.8%