Discrete inputs/outputs

135

10

Input relay blocks

• GND

Connects directly to common on power terminal strip

No daisy-chaining GND to other relay blocks or “OR” boards

Inputs from the PMC464 must have a common connection from the PMC464 (pin 17)
running inside cable bundle

This common connection from the PMC464 must connect to the relay board’s GND

• +5V

One connection directly to +5V power terminal strip

All additional 5V connections on a single relay input block are daisy-chained within its
own individual input relay block

Output relay blocks
• GND

Redundant output

GND connected to GND point on the “OR” board

All additional GND connections on a single relay output block are daisy-chained
within its own individual output relay block

No daisy-chaining GND to other relay blocks or “OR” boards

Non-redundant output

GND connected to common on power terminal strip

No daisy-chaining GND to other relay blocks

Outputs from the PMC464 must have a common connection from the PMC464 (pin 17)
running inside cable bundle

Common connection from PMC464 card should connect to its corresponding
output relay block

Connect PMC464 common to output relay block GND

• +5V

N/A

“OR” board
• +5V

Connect directly to +5V on power terminal strip

• GND

Connect directly to common on power terminal strip

No daisy-chaining GND to other “OR” boards or relay blocks

Output from PMC464 must have a common connection (pin 17) running inside the cable
bundle

Common connection from PMC464 connects to its corresponding “OR” Board

• Twist 5V and GND cables together before connecting to power terminal strip

Power supply
• +5V

Connect directly to +5V on power terminal strip

• GND

Connect directly to GND on power terminal strip