Alarms and events description and system troubleshooting guide

225

A

Invalid Setting ST From CPUB
Change Rejected

Messenger has received an invalid short time
enable or disable setting from CPU B and has
rejected the value

This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting ST Change
Rejected” or “Invalid Setting ST Pickup
Change Rejected” event. See the description
of those events for details.

Invalid Setting GF From CPUA
Change Rejected

Messenger has received an invalid ground
fault enable or disable setting from CPU A
and has rejected the value

This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting GF Change
Rejected” or “Invalid Setting GF Pickup
Change Rejected” event. See the description
of those events for details.

Invalid Setting GF From CPUB
Change Rejected

Messenger has received an invalid ground
fault enable or disable setting from CPU B
and has rejected the value

This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting GF Change
Rejected” or “Invalid Setting GF Pickup
Change Rejected” event. See the description
of those events for details.

Note Messngr Ignored Invalid
Command CPUA

Messenger has received an invalid command
from CPU A and will ignore it

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Messngr Ignored Invalid
Command CPUB

Messenger has received an invalid command
from CPU B and will ignore it

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Messngr Arbitrated
Command From CPUA

Messenger has received conflicting
commands from CPU A

Examine event logs from both CPUs to
determine if CPUs sent conflicting
commands at approximately the same time.

Note Messngr Arbitrated
Command From CPUB

Messenger has received conflicting
commands from CPU B

Examine event logs from both CPUs to
determine if CPUs sent conflicting
commands at approximately the same time.

Note Messngr Reports CPUA
Command Timed Out

Command sent to Messenger from CPU A has
timed out

• Verify that breaker is in the Test or

Connect position.

• If Open command timed out, check shunt

trip fuse.

• If Close command timed out, verify that

breaker is an electric breaker. If it is, verify
that closing spring is charged, also check
the fuse for the charging motor.

• Contact GE Post Sales Service (see

How

to contact us on page 2

).

Note Messngr Reports CPUB
Command Timed Out

Command sent to Messenger from CPU B has
timed out

Same as CPU A above.

CPUA Synch Clock OK

Messenger reports that CPU A is using the
CPU Synch Clock (event recorded by CPU B)

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips