GE Industrial Solutions Entellisys System User Manual User Manual

Page 223

Advertising
background image

Alarms and events description and system troubleshooting guide

223

A

Invalid Setting IOC Pickup
Change Rejected

Attempt to change IOC pickup setting has
been rejected

The value entered for the IOC pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Invalid Setting GF Change
Rejected

Attempt to enable or disable ground fault has
been rejected

The setting entered for GF enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting GF Pickup
Change Rejected

Attempt to change the ground fault pickup
setting has been rejected

The value entered for the GF pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Invalid Setting ST Change
Rejected

Attempt to enable or disable short time has
been rejected

The setting entered for ST enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting ST Pickup Change
Rejected

Attempt to change the short time pickup
setting has been rejected

The value entered for the ST pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Messenger/Breaker Config Status

Caution Messngr Control Power
1 Lost

Messenger reports that it has lost control
power source 1

• Check LINE LED on UPS. If it is off, check

the main power switch on the UPS. If it is
off, turn it on. Otherwise, check the
control power fuse between the
transformer and the UPS.

• If the LINE LED is on, check the ON LINE

LED. If it is off, see the UPS manual.

• Check UPS fuse.
• Contact GE Post Sales Service (see

How

to contact us on page 2

).

Caution Messngr Control Power
2 Lost

Messenger reports that it has lost control
power source 2

Same as control power 1 lost

Messngr Control Power 1 OK

Messenger reports that control power source
1 is present

Messngr Control Power 2 OK

Messenger reports that control power source
2 is present

Note Invalid Breaker Type

Messenger reports a breaker type other than
ANSI

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips