Multipoint functions

92

7

Figure 7-4 Bus differential alarms setup

7.1.2 Troubleshooting

Bus Differential Setting Change Rejected events are observed in the Sequence of Events log
• Verify that the pickup setting is within the valid range. Valid range is from “Zone Minimum

Pickup” to 22,000 Amps. (See

Setting Bus Differential pickups/delays on page 90

.)

Frequent suspended/resumed events are seen
• Verify that both CPUs are operating with the hardware clock. This can be done from the

System Health screen. The Synchronization hardware OK indicator lights should be green for
both CPUs.

7.1.3 Events generated by the Bus Differential Relay

To view a table of the events generated by the Bus Differential Relay, see

Alarms and events

on page 187

.

7.1.4 Alarms generated by the Bus Differential Relay

To view a table of the alarms generated by the Bus Differential Relay, see

Alarms and events

on page 187

.