Alarms

178

13

The legend across the top of the Alarm Status screen shows the possible states for alarm
conditions.

When an alarm first occurs, it transitions from a green state to a flashing red state. It remains in
a flashing red state until it is acknowledged by an operator or the condition goes away (and
transitions to solid red or yellow respectively). The alarm returns to a green state when the
condition is normal and acknowledged.

NOTE: Transient events that occur quickly (such as an ST overcurrent trip) may appear to
transition directly from green to yellow since the circuit breaker clears the fault in such a short
period of time.

Alarms can be acknowledged individually with the acknowledge button adjacent to each alarm,
or all at once by clicking Acknowledge All. The alarm states are maintained by the CPU
controller, so that the displayed state is consistent across both local and remote HMIs.

13.3 Troubleshooting

Alarms are setup to send e-mail notifications, but notifications are not received
• Make sure that the firewall is configured to allow communication between the specified

e-mail server and the HMI.

Table 13-1 Alarm conditions

Alarm Color

Meaning

Green

Normal – The condition is not currently nor has
since the last acknowledgment been persistent.

Red (Flashing)

Active / Unacknowledged – The condition is
currently persistent and has not been
acknowledged by an operator.

Red (Solid)

Active / Acknowledged – The condition is currently
persistent but has been acknowledged by an
operator.

Yellow

Inactive / Unacknowledged – The condition was
persistent and currently is not, but it has not been
acknowledged by an operator.

Gray

The alarm function is not currently communicating
with the default CPU to obtain updates of the
condition status.