GE Industrial Solutions Entellisys System User Manual User Manual

Page 209

Advertising
background image

Alarms and events description and system troubleshooting guide

209

A

User With [USER ID] ID Logged
Into HMI

Indicates that the specified operator has
logged into the HMI application

User With [USER ID] ID Logged
Off HMI

Indicates that the specified operator has
logged out of the HMI application

Caution: Unable to Read HMI
Config File(elvs_config.bcf).
Defaults Loaded

The HMI was unable to load the local
configuration file from disk.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

HMI Config File Loaded OK

The HMI successfully loaded the local
configuration file from disk.

Caution: Error Saving HMI
Config File

The HMI was unable to successfully store the
local configuration file to disk.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

HMI Config File Saved OK

The HMI successfully loaded the local
configuration file from disk.

HMI is restarted for Periodic
maintenance

The HMI has restarted itself as part of its
periodic self-maintenance routine.

HMI/CPU Communications Related

Troubleshooting communications between
an HMI and a CPU:
• Check power to System Interface

Ethernet Switch.

• Check power and status of CPU.
• Check communications link status. LEDs

at the Ethernet ports on the HMI, switch,
and CPU should be green.

• Check communications with redundant

CPU by establishing it as the Primary
(default) unit.

• Verify that the IP address, subnet mask,

and gateway address (if applicable) are
compatible between the CPU and HMI.

If this does not reveal the source of the
problem, contact GE Service.

HMI Resumed Communication
with [CPUA/B]

Logged when HMI establishes
communications with a CPU

HMI Lost Communication with
[CPUA/B]

Logged when HMI can no longer
communicate with a CPU

HMI couldn't Establish
Communication with [CPUA/B]

Logged when HMI cannot establish a
communications session with a CPU

IP Address for CPUA Set To
[n.n.n.n] From [n.n.n.n]

Logged to record a change in the IP address
for the given CPU

IP Address for CPUB Set To
[n.n.n.n] From [n.n.n.n]

Logged to record a change in the IP address
for the given CPU

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips

Advertising