GE Industrial Solutions Entellisys System User Manual User Manual

Page 218

Advertising
background image

Alarms and events

218

A

Alarm Dropout Bus Diff Zone
1…4 Settings 1

Alarm only bus differential for zone 1…4,
settings 1 has dropped out of pickup

Alarm Bus Diff Zone 1…4
Settings 1

Alarm only bus differential for zone 1…4,
settings 1 has operated

Alarm Pickup Bus Diff Zone 1…4
Settings 2

Alarm only bus differential for zone 1…4,
settings 2 has entered pickup

Alarm Dropout Bus Diff Zone
1…4 Settings 2

Alarm only bus differential for zone 1…4,
settings 2 has dropped out of pickup

Alarm Bus Diff Zone 1…4
Settings 2

Alarm only bus differential for zone 1…4,
settings 2 has operated

Protection Disabled Invalid Cfg
Bus Diff

File that contains configuration information
for bus differential is bad or missing, all bus
differential functions are disabled

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Protection Suspended Zone 1…4
Bus Diff

Bus differential (trip and alarm only) for zone
1…4 has been suspended

Examine Sequence of Events for cause. It can
be any one of the following:
• Current on one or more phases exceeded

10X (overcurrent pickup/trip event)

• Messenger at a breaker in the zone is not

communicating (Caution CPU Not Rcv
From Messngr)

• Messenger at a breaker in the zone has

been decommissioned (Attention
Messngr Decommssned Msg Proto Ver,
Attention Messngr Decommssned Dupe
IDs Seqs, or Attention Messngr
Decommssned Dupe Ids)

• A Compartment ID button at a breaker in

the zone has been misconfigured

• At least one of the breakers in the zone

has been put into test mode (Test Mode
Initiated from Test Kit)

Protection Resumed Zone 1…4
Bus Diff

Bus differential (trip and alarm only) for zone
1…4 has resumed

Invalid BusDiff Zone1…4 Set1
Pkup Chng Rejctd

Pickup setting 1 for bus differential for zone
1…4 is too low, change is rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid BDiff Zone1…4 Set1 Alm
Pkup Chng Rejctd

Pickup setting 1 for alarm only bus
differential for zone 1…4 is too low, change is
rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid BusDiff Zone1…4 Set2
Pkup Chng Rejctd

Pickup setting 2 for bus differential for zone
1…4 is too low, change is rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid BDiff Zone1…4 Set2 Alm
Pkup Chng Rejctd

Pickup setting 2 for alarm only bus
differential for zone 1…4 is too low, change is
rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Table A-2 Sequence of events description and troubleshooting guide

Event