Alarms and events

234

A

Breaker Close Command
Rejected Breaker Locked Out

Breaker is locked out, so CPU has rejected
the close command

• If breaker has a manual lockout, verify

that the lockout has been reset.

• If the breaker has a network interlock, the

control logic is likely causing the breaker
to reject the close command.

• Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention IO Card Detection
Mismatch Found 0 of 1

CPU expected 1 digital I/O card, but detected
none

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 0 of 2

CPU expected 2 digital I/O cards, but
detected none

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 1 of 0

CPU expected no digital I/O cards, but
detected 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 1 of 2

CPU expected 2 digital I/O cards, but
detected 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 2 of 0

CPU expected no digital I/O cards, but
detected 2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 2 of 1

CPU expected 1 digital I/O card, but detected
2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips