Alarms and events description and system troubleshooting guide

217

A

Alarm Dropout Overfrequency

Alarm only overfrequency relay has dropped
out of pickup

Voltage Below Overfreq Alarm
Blocking Voltage

The voltages on all three phases have
dropped below the alarm only overfrequency
blocking voltage threshold.

Voltage Above Overfreq Alarm
Blocking Voltage

The voltage on at least one of the three
phases has exceeded the alarm only
overfrequency blocking voltage threshold.

Pickup Overfrequency

Overfrequency relay has entered pickup

Breaker Trip Overfrequency

Overfrequency relay has operated

Dropout Overfrequency

Overfrequency relay has dropped out of
pickup

Voltage Below Overfrequency
Blocking Voltage

The voltages on all three phases have
dropped below the overfrequency blocking
voltage threshold.

Voltage Above Overfrequency
Blocking Voltage

The voltage on at least one of the three
phases has exceeded the overfrequency
blocking voltage threshold.

Relays - Bus Differential

Pickup Bus Diff Zone 1…4
Settings 1

Bus differential for zone 1…4, settings 1 has
entered pickup

Dropout Bus Diff Zone 1…4
Settings 1

Bus differential for zone 1…4, settings 1 has
dropped out of pickup

Breakers Trip Bus Diff Zone 1…4
Settings 1

Bus differential for zone 1…4, settings 1 has
operated and tripped the breakers

Breakers Trip Backup Bus Diff
Zone 1…4 Settings1

Bus differential backup for zone 1…4, settings
1 has operated and tripped the breakers

Pickup Bus Diff Zone 1…4
Settings 2

Bus differential for zone 1…4, settings 2 has
entered pickup

Dropout Bus Diff Zone 1…4
Settings 2

Bus differential for zone 1…4, settings 2 has
dropped out of pickup

Breakers Trip Bus Diff Zone 1…4
Settings 2

Bus differential for zone 1…4, settings 2 has
operated and tripped the breakers

Breakers Trip Backup Bus Diff
Zone 1…4 Settings2

Bus differential backup for zone 1…4, settings
2 has operated and tripped the breakers

Alarm Pickup Bus Diff Zone 1…4
Settings 1

Alarm only bus differential for zone 1…4,
settings 1 has entered pickup

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips