Alarms and events

212

A

Clock and Time Synchronization Related

Time Synchronization Disabled

Logged to record that the HMI is no longer
synchronizing the real-time clock on each
CPU

Time Synchronization Enabled

Logged to record that the HMI is now
synchronizing the real-time clock on each
CPU

Time Synchronization
Frequency Set To [NN] Hours

Logged to record a change in the setting
which determines how often the HMI
synchronizes the real-time clock on each
CPU

Time Synchronization
Successful

Logged each time the HMI synchronizes the
real-time clock on each CPU

Caution: Time Synchronization
Failed with [CPU A/B]

Logged when the HMI is unable to
synchronize the real-time clock of a given
CPU

See the communications troubleshooting tips
above (

Troubleshooting communications

between an HMI and a CPU: on page 209

).

Caution: Daylight Savings Time
Error X

The HMI was unable to resolve the time zone
settings

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Daylight Savings Time in Effect,
Time Synchronized

Logged when a daylight savings transition
and resynchronization occurs

Standard Time in Effect, Time
Synchronized

Logged when a return to standard time and
resynchronization occurs

CPU Settings Related

Default CPU set to CPUA

The default view for the HMI has been set to
CPU A

Default CPU set to CPUB

The default view for the HMI has been set to
CPU A

Messnger Commission
Command Sent for Breaker
[Name]

Logged when a command to commission an
Entelliguard Messenger is issued to a CPU

Messnger Decommission
Command Sent for Breaker
[Name]

Logged when a command to decommission
an Entelliguard Messenger is issued to a CPU

Frequency Set To [50/60]Hz for
[CPUA/B]

Logged to record a change in the frequency
setting for a given CPU

Caution: Settings Failed Writing
Frequency to [CPUA/B]

Logged to indicate that a request to change
the system frequency of a given CPU was
rejected

Also check the event log for communications
errors within the general time frame in which
this event occurred. See the communications
troubleshooting tips above if this is the case
(

Troubleshooting communications between

an HMI and a CPU: on page 209

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips