Viewing and understanding PM data

171

12

If the current flowing through the circuit breaker at the time of transition exceeds the maximum
current threshold (Table 12-2), exactly 45% of the circuit breaker life is added to the total load
life used value.

Table 12-1 K values for various frame sizes

Frame Size

K

frame

800

2800

1600

1200

2000

1000

3200

600

4000

500

5000

400

Table 12-2 Maximum Current Thresholds for various frame ratings, expressed in multiples of CT rating

Frame Size

Max current
threshold

800

15

1600

15

2000

15

3200

13

4000

9

5000

7