Alarms and events description and system troubleshooting guide

221

A

Invalid Set MSGF Zone1…4 Alrm
Pkup Min Used

Pickup setting 1 for alarm only multi source
ground fault for zone 1…4 has been set to the
minimum allowable (current setting is too
low)

Check pickup setting for MSGF zone. Value
can be set higher if desired.

Invalid MSGF Sum Zone1…2
Pkup Chng Rejctd

Pickup setting for multi source ground fault
for summation zone 1…2 is too low, change is
rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid MSGF Sum Zone1…2 Alrm
Pkup Chng Rejctd

Pickup setting for alarm only multi source
ground fault for summation zone 1…2 is too
low, change is rejected

Set pickup value above the minimum allowed
(20% of the smallest CT rating in the zone);
CPU sets value to minimum in this case.

Invalid MSGF Sum Zone1…2
Pkup Min Used

Pickup setting for multi source ground fault
for summation zone 1…2 has been set to the
minimum allowable (current setting is too
low)

Check pickup setting for MSGF Summation
zone. Value can be set higher if desired.

Invalid MSGF Sum Zone1…2 Alrm
Pkup Min Used

Pickup setting 1 for alarm only multi source
ground fault for summation zone 1…2 has
been set to the minimum allowable (current
setting is too low)

Check pickup setting for MSGF Summation
zone. Value can be set higher if desired.

Relays – High Resistance GF

Pickup High Resistance GF

High resistance ground fault has entered
pickup

Dropout High Resistance GF

High resistance ground fault has dropped out
of pickup

Alarm High Resistance GF

High resistance ground fault alarm has
operated

Invalid Settings HRGF Unable To
Detect Phase

The product of the pickup current setting and
the ground resistance setting is greater than
the nominal phase voltage

Check pickup current and ground resistance
settings.

Relays – Synch Check

Synch Check Control Enabled
1…6

Synch check relay 1…6 has been enabled

Synch Check Control Disabled
1…6

Synch check relay 1…6 has been disabled

Synch Check 1…6 Sources Not
Synchronized

Messengers that are providing voltage
information for synch check relay are not
synchronized, so the CPU is unable to check
for synchronization between voltage sources.

This should only happen on start-up, or when
a Messenger is connected to the system (or
rebooted). If it happens repeatedly during
normal operation, contact GE Post Sales
Service (see

How to contact us on page 2

).

Synch Check 1…6 Sources Not
Compatible

Voltage sources for synch check relay 1…6
are not compatible; i.e., they have different
PT configurations or ratings

• Verify that the Source Voltages for the

synch check relay are correct.

• Verify that the source voltages have the

correct PT configurations.

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips