4 alarm settings – GE Industrial Solutions Entellisys System User Manual User Manual
Page 74
Single point functions
74
5
Delay: Adjust the reverse power delay from 0.1 to 600 seconds in increments of 0.5 seconds
from the Time Delay drop-down menu.
Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.
5.2.6.4 Alarm settings
Relay Enabled: Select Enabled to enable the relay.
Pickup: Adjust the reverse power pickup from 10 to 990kW in increments of 10kW from the
Pickup Setting drop-down menu.
Delay: Adjust the reverse power delay from 0.1 to 600 seconds in increments of 0.5 seconds
from the Time Delay drop-down menu.
Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.
Figure 5-9 Reverse Power Relay settings