Alarms and events

224

A

Protection Defaulted Invalid
Frame Rating

Messenger reports a frame rating value that
is not valid, protection settings set to values
that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid CT
Rating

Messenger reports a CT rating value that is
not valid, protection settings set to values
that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Frame And
CT Mismatch

Messenger reports frame and CT ratings that
are inconsistent, protection settings set to
values that are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid
Rating Switch

Messenger reports a rating switch value that
is not valid, protection settings set to values
that are safe for all frame sizes

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Check Switch Invald LT
Overcurrent Set

Messenger reports a long time overcurrent
protection pickup setting that is not valid

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution Enet Cable
Disconnected Messngr CPUA

Messenger reports that it has no ethernet
connection to CPU A

Check connection between CPU A and
switch, and the switch and the Messenger.

Caution Enet Cable
Disconnected Messngr CPUB

Messenger reports that it has no ethernet
connection to CPU B

Check connection between CPU B and
switch, and the switch and the Messenger.

Attention Messngr Synch
Disabld Bad Freq CPUA

Messenger has received an invalid system
frequency from CPU A and will not be able to
synchronize from it

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Synch
Disabld Bad Freq CPUB

Messenger has received an invalid system
frequency from CPU B and will not be able to
synchronize from it

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Invalid Setting IOC Mult CPUA
Chng Rejected

Messenger has received an invalid IOC
pickup setting from CPU A and has rejected
the value

This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.

Invalid Setting IOC Mult CPUB
Chng Rejected

Messenger has received an invalid IOC
pickup setting from CPU B and has rejected
the value

This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.

Invalid Setting ST From CPUA
Change Rejected

Messenger has received an invalid short time
enable or disable setting from CPU A and has
rejected the value

This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting ST Change
Rejected” or “Invalid Setting ST Pickup
Change Rejected” event. See the description
of those events for details.

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips