CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

100

Enable-Disable Info: Displays the enable/disable status of the following features:

Temp Comp

Temperature compensation

Low Temp Comp

Low temperature compensation

Recharge Ilim

Recharge current limit

Auto Boost

Automatic boost charge

Auto Batt Test

Automatic battery test

Rect Redund

Rectifier redundancy

Mid-Cell V Mon

Mid-cell voltage monitoring

Imminent Shutdn

Imminent system shutdown alarm (LVBD)

Local Write

Whether or not the system can be configured through the local port.

Modem Write

Whether or not the system can be configured through the modem port.

System Info: Various high level system statuses.

Controller Info

Provides the versions of software for the overall controller
(QS840A_MC1), boot block of the controller, display, and the defaults.

Date

System controller present date using configured format.

Time

System controller present time using configured format.

Ambient Temperature

System controller present temperature using configured format.

Control/Operations

The following are the system control and operation functions that can be performed from the
front panel. These operations are generally used in post installation and maintenance modes.

Start Lamp Test

Temporarily illuminates all status indicators of attached rectifiers,
distribution monitoring and control modules and the system
controller.

Restart Rectifiers

Restarts all system serial controlled rectifiers. Does not affect
rectifiers, and other system devices that are already functioning.

Clear Events

Used to clear momentary events or alarms. It clears the following
system alarms: Check Battery, Reserve Time Low, Battery
Voltage Imbalance

Uninstall Equipment

Clears alarms related to the removal of a system component such
as a rectifier, thermal probe, or voltage monitoring module.

Alarm Test

Initiates the asserting the Form-C alarms.

Start Battery Test

Initiates the manual battery test feature. A stop battery test
operation is displayed to interrupt the testing and return the unit to
normal operation. The manual battery test utilizes the configured
test duration and a system bus voltage threshold to represent the
end of reserve.

Start Boost

Initiates the manual battery Boost feature. A stop battery Boost
operation is displayed to interrupt the Boost operation mode and
return the unit to normal operation.