Distribution Module GMT Fuses

The following GMT fuses have been accepted for use in dc load applications, are available
for the current Distribution Module.

Size (Amps)

Comcode

Size (Amps)

Comcode

0.25 405006222

7.5

405725433

0.5 406976894

10

406159236

1.33 405673146

12

407845197

2 405181983

15

406473959

3 406976985

20

408555453

5 406159061

The following shows the possible fuse loading scenario for the Single-Slot and Double-Slot
Distribution Modules. 20A fuse positions can be used only with factory wiring. When using
20A fuses, adjacent fuse positions must be left open.

For the Single-Slot Distribution Module with 10 GMT fuses, Field installation is only rated
for 10A fuses. No more than 80A may be carried through the 10 fuse positions, or 40A
through each half section. 15A and lower rated fuses may be used in any combination and
position, as long as they do not violate the previous 80A/40A rule.

For the Single-Slot Distribution Module with 5 GMT fuses, a maximum load of 32 A is
permitted with restrictions on the fuse positions. Specifically:

Position F1 defined

as the bottom fuse position and F5 as the top fuse position.

1. Configuration #1 - F1+F2 <= 15A, F3<=

1

5A, and F5+F4<= 10A

2. Configuration #2 - F1<=15A; F2=No Fuse; F3<=15A; F4=No Fuse; F5<=10A 3.

For the Double-Slot Distribution Module, each 8-fuse board can support a maximum of 80A.

Single-Slot Distribution Module

Double-Slot

Distribution Module

Position

Max Fuse

Position

Max Fuse

Position

Max Fuse

10

10

15A

8

15A/20A

9 20A

9

7

8

8

15A

6

15A/20A

7 20A

7

5

6

6

15A

4

15A/20A

5

5

3

4 20A

4 15A

2 15A/20A

3

3

1

2 20A

2 15A

1

1

15A

(Arrows indicate

alternate positions)