Control/operations, System info – GE Industrial Solutions CPS6000 User Manual

Page 119

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

119

System Info

This section of the menu displays various high level system status.

Controller Info

Provides software versions for overall controller, boot block , display, and
web pages. It also provides the file used for factory defaults along with its
version number. For the NX400, the display is of the format (vNX.d.d).

Date

System controller present date using configured format.

Time

System controller present time using configured format.

Ambient Temperature

System controller present temperature of its on-board sensor using
configured format.

Control/Operations

The following are the system control and operation functions that can be performed from the
front panel. These operations are generally used in post installation and maintenance modes.

Start Lamp Test

Temporarily illuminates all status indicators of attached rectifiers, distribution
monitoring and control modules and the system controller.

Restart Devices

Provides the ability to restart “All” system serial controlled rectifiers at once or
individually resetting rectifiers or ringers. Does not affect rectifiers, ringers,
and other system devices that are already functioning.

Clear Events

Used to clear momentary events or alarms. It clears the following system
alarms: Check Battery, Reserve Time Low, Battery Voltage Imbalance

Uninstall
Equipment

Clears alarms related to the removal of a system component such as a rectifier,
thermal probe, or voltage monitoring module.

Clear History

This area of the menus system can be used to clear the various items that the
controller maintains history records. Once cleared the controller begins to keep
history of new events.

Alarm History

Operation to only clear alarm event history.

BD History

Operation to only clear BD network access history.

Rectifier History

Operation to only clear rectifier event history.

Boost History

Operation to only clear Boost event history.

Local Port History

Operation to only clear local port access history.

Modem History

Operation to only clear Modem port access history.

Network History

Operation to only clear network access history.

All History

Allows a single command operation to clear all history

records from the QS841.

Clear Statistics

This area of the menus system can be used to clear the various items that the
controller maintains statistical records. Once cleared the controller begins to
keep new statistical data.

Clear Basic - This operation allows the user to clear individually or as a group
the Basic statistical data kept on Plant Load, the highest battery temperature,
and ambient.
Clear Trend - This operation allows the user to clear the trend data kept on the
plant load.
Clear BD - This operation allows the user to clear the Battery on Discharge
(BD) statistics kept on the plant load and voltage during discharge.

Alarm Test

Initiates the Form-C alarm test by asserting each of the configured Form-C
alarms at the configured alarm interval.