CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

174

Rectifiers Related

Commands

obj,attr

description sta

cha

ope

type range

of

values

gsr,stt Individual

rectifier

state r x text “ON”,

“OFF”,

“STANDBY”,

“MISSING”
Only “ON” and “STANDBY”
can be used with ope.

gsr,adc Individual

rectifier

current x

number ddd

s stands for shelf number (1, 2, or 3)
r stands for rectifier number (1 to 5)

Individual Rectifier State: When requested, shows the state of the individual

rectifiers. Note that the rectifier numbering starts from the left-most position of the

master shelf (shelf number 1.)

When obtaining individual rectifier status information, the following information may

be transmitted:

ON: Rectifier operating normally. User may use ope to turn ON a rectifier in standby.

OFF: Rectifier has been shutdown due to hardware failure.

STANDBY: User has inhibited the rectifier's output voltage. User may use ope to

place a rectifier into a standby condition.

MISSING: An acknowledged rectifier has been removed.

VACANT: Rectifier has not been installed in that position.

Rectifiers may also be put in standby; however, the ability to place rectifiers in

standby requires some backup plan to take the rectifier out of standby automatically

under a low voltage condition. The battery on discharge (BOD) threshold is used as a

rectifier-on voltage threshold. In other words, when the plant voltage dips below the

BOD threshold, the controller turns on all rectifiers that are in standby.

Individual Rectifier Current: When requested, shows the current output from an

individual rectifier.