GE Industrial Solutions CPS6000 User Manual

Page 161

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

161

Controller

LED

(Note 3)

User Interface

Display

Rectifier LEDs

(Note 4)

AC DC ALM

Ringer

LED

Distribution

Module

Board LED

Possible Problem(s)

Possible Solution(s)

RED MAJ,

Major

Communication Fail

G G o

-R-

(or missing

LVD Board)

LVD Board lost
communication with the
controller.

1. Replace Distribution Module

Board. (Note 2)

2. If problem persists, call your

local field representative.

RED MAJ,

Major

Communication Fail
Minor Ringer
Redundancy

o

(or

missing
Ringer)

No Ringers installed in a
Ringer Chassis.
Ringers not fully seated in
Ringer Chassis.

1. Fully seat Ringers in Ringer

Chassis.

2. Install Ringers in Ringer

Chassis.

3. If problem persists, call your

local field representative.

AMBER MIN,

AC

Fail

o o o

Single Rectifier not
receiving ac power.

AC input circuit breaker
has opened.

AC input voltage is out
of range.

1. Verify ac power to rectifier is

available.

2. Verify rectifier input circuit

breaker is closed.

3. If problem not corrected, replace

rectifier.

AMBER

MIN, Rectifier Fail
(Note 1)

G

o

o

Rectifier output has dropped
below 36V, rectifier has
entered hiccup mode.

Replace rectifier.

AMBER

MIN, Battery High
Temperature G

G

o

Batteries have exceeded
temperature threshold set by
user.

Call your local field representative.

AMBER MIN,

Thermal

Probe Fail

G G o

Battery thermal probe failed.

1. Ensure thermal probe is properly

connected to thermal probe
cable.

2. Ensure cable is properly

connected to the rear of the
Distribution Module.

3. If problem persists, replace

thermal probe per ensuing
instructions.

4. If problem still persists, call your

local field representative.

AMBER

MIN, Rectifier Fail

G o R

Single rectifier thermal
alarm: Excessive ambient
temperature Multiple
rectifier failure

1. Verify that there is no

obstruction of the vertical
airflow path.

2. Reset the rectifier by removing

the rectifier, waiting
approximately 30 seconds, and
replacing the rectifier.

3. If problem persists, replace the

rectifier.

4. If problem still persists, call your

local field representative.

AMBER MIN,

Minor

Communication Fail

(Single Rectifier
signaling)

-R-

Rectifier lost
communication with
controller.

1. If a rectifier has been removed

from an installed/operational
system, go to the
Control/Operations menu and
execute Uninstall Equipment.

2. Reset the rectifier by removing

the rectifier, waiting
approximately 30 seconds, and
replacing.

3. If problem persists, replace the

rectifier.

4. If problem still persists, call your

local field representative.

AMBER

MIN, Minor Ringer
Redundancy

R

(or

missing
Ringer)

Failed Ringer.
Missing redundant Spare
Ringer.

Replace failed Ringer.
Install missing Ringer.

AMBER

MIN, Minor Ringer
Redundancy
Minor Ringer Fail

R

Failed Ringer.
Missing redundant Spare
Ringer.

Replace failed Ringer.
Install missing Ringer.