CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
208
ES648B Comments
cha faj1,acc=R3
Enable relay R3 as Major Fuse Alarm
cha mrfa1,acc=""
Disable relay R3 as Multiple Rectifier Fail alarm
cha mrfa1,sev=MIN
Change Multiple Rectifier Failure from MAJ to MIN
cha bts1,acc=""
Disable relay R4 as Plant Battery Test Active
cha vla1,acc=R4
Enable relay R4 as Low Voltage Alarm
cha macfl,acc=""
Disable relay R2 as Multiple AC Fail
cha macfl,sev=MIN
Change Multiple Rectifier Failure to MIN
cha bda1,sev=RO
Change Battery On Discharge from PMJ to RO
cha rls1,acc=""
Disable relay R3 as Redundancy Loss
cha rfa1,sev=MIN
Change Single Rectifier Failure to MIN
cha rfa1,acc=""
Disable all relays for Single Rectifier Fail alarm
cha bta1,sev=MAJ
Change High Battery Temperature from MIN to MAJ