GE Industrial Solutions CPS6000 User Manual

Page 208

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

208

ES648B Comments

cha faj1,acc=R3

Enable relay R3 as Major Fuse Alarm

cha mrfa1,acc=""

Disable relay R3 as Multiple Rectifier Fail alarm

cha mrfa1,sev=MIN

Change Multiple Rectifier Failure from MAJ to MIN

cha bts1,acc=""

Disable relay R4 as Plant Battery Test Active

cha vla1,acc=R4

Enable relay R4 as Low Voltage Alarm

cha macfl,acc=""

Disable relay R2 as Multiple AC Fail

cha macfl,sev=MIN

Change Multiple Rectifier Failure to MIN

cha bda1,sev=RO

Change Battery On Discharge from PMJ to RO

cha rls1,acc=""

Disable relay R3 as Redundancy Loss

cha rfa1,sev=MIN

Change Single Rectifier Failure to MIN

cha rfa1,acc=""

Disable all relays for Single Rectifier Fail alarm

cha bta1,sev=MAJ

Change High Battery Temperature from MIN to MAJ

Advertising