GE Industrial Solutions CPS6000 User Manual

Page 171

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

171

Alarm Thresholds/Relays

Related Commands

obj,attr

description sta

cha

ope

type

range

of

values

macf1,sev Multiple AC fail severity

x x

text “MAJ”, “MIN” , or “RO"

mcm1,acc Major

communication

relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

mcm1,ast Major

communication

alarm

state

x

number 0:not

active

1:active

mcm1,sev Major

communication

severity

x x

text “MAJ”, “MIN” , or “RO"

mrfa1,acc Multiple rectifier fail relay

x x

text

“R1” ,“R2”, “R3”, “R4,” or “”

mrfa1,ast Multiple rectifier fail alarm state

x

number 0:not

active

1:active

mrfa1,sev Multiple rectifier fail severity

x x

text “MAJ”, “MIN” , or “RO"

osa1,acc

Open string alarm relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

osa1,ast

Open string alarm state

x

number 0:not

active

1:active

osa1,sev

Open string alarm severity

x x

text “MAJ”, “MIN” , or “RO"

rfa1,acc

Rectifier fail relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

rfa1,ast

Rectifier fail alarm state

x

number 0:not

active

1:active

rfa1,sev

Rectifier fail severity

x x

text “MAJ”, “MIN” , or “RO"

rls1,acc

Rectifier redundancy loss relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

rls1,ast

Rect redundancy loss alarm state

x

number 0:not

active

1:active

rls1,sev

Rect redundancy loss severity

x x

text “MAJ”,

MIN” , or “RO"

scd1,acc

Battery voltage imbalance relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

scd1,ast

Battery voltage imbalance alarm state

x

number 0:not

active

1:active

scd1,sev

Battery voltage imbalance severity

x x

text “MAJ”, “MIN” , or “RO"

tpa1,acc

Thermal probe fail relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

tpa1,ast

Thermal probe fail alarm state

x

number 0:not

active

1:active

tpa1,sev

Thermal probe fail severity

x x

text “MAJ”,

MIN” , or “RO"

vmf1,acc Voltage module fail relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

vmf1,ast

Voltage module fail alarm state

x

number 0:not

active

1:active

vmf1,sev Voltage module fail severity

x x

text “MAJ”,

MIN” , or “RO"

vsf1,acc

Sense voltage fail relay

x x

text

“R1” ,“R2”, “R3”, “R4”, or “”

vsf1,ast

Sense voltage fail alarm state

x

number 0:not

active

1:active

vsf1,sev

Sense voltage fail severity

x x

text “MAJ”, “MIN” , or “RO"

The previous table outlines the various alarms that are available through the QS840A

controller. Refer to Alarm Relays in Appendix C for more details. The QS840A

controller is provided with two severity relays and two relays that may be assigned to

any combination or all of the alarms noted above.

The controller is shipped with PMN assigned to Alarm Relay 2 and PMJ to Alarm

Relay 1. Also, for each alarm condition noted above, the factory severity is noted in

bold. The user may change the severity of configurable alarms from the factory set

severity. Note that the alarms noted above may also be assigned a severity of RO

(Record Only). If so assigned, the alarm condition will be transmitted without any

PMJ or PMN severity.