GE Industrial Solutions CPS6000 User Manual
Page 182
CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
182
his Report
Boost
History
Syntax:
his bs1,stt
Description
This command reports the boost history in the following format:
sum bs1,stt
30-MAY-03,15:11:12,RESUMED,COMPLETED,78
30-MAY-03,12:03:34,AUTO,DISCHARGE,14
.
**
This report gives the start date, start time, start reason, stop reason, and boost duration in
minutes. The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge
RESUMEDBoost resumed after being suspended by a discharge
The stop reasons are:
COMPLETEDBoost completed normally
TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge
CANCELEDBoost canceled by user
ALARMBoost cancelled by an alarm condition
DISABLEDAuto boost cancelled by being disabled