GE Industrial Solutions CPS6000 User Manual

Page 175

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

175

Battery Reserve Management

Related Commands

obj,attr description sta

cha

ope

type

range

of

values

br1,hbt Highest

battery

temperature

x

number dd °C

br1,adc

Total battery current

x

number d A (+ for discharge, - for

charge)

br1,bts

Plant battery test (lower rect V)

x x

number 0:stop 1:start

br1,scd

Battery voltage imbalance detection
enable

x

number 0:disable

1:enable(Automatically
enabled when mid cell V
monitor present)

br1,ntm

Number of temperatures present

x d

br1,nvm

Number of mid-cell V present

x d

br1,cle

Recharge current limit enable

x x number 0:disable 1:enable

br1,clt

Recharge current limit threshold

x x number 5-100:10

br1,btr Discharge

test

results

x text “???”

br1,btc Battery

type

x x text ìFLOODEDî,

ìVALVE-

REGî

br1,bte

Auto test enable

x x number 0:disable 1:enable

br1,atd Auto

test

date

x x date dd-mmm-yy

br1,ath

Auto test start hour

x x number 0-23:0

br1,atw

Auto test min hours after BD

x x number 0-240:0 hours

br1,tin

Auto test interval

x x number 1-18:12 months

br1,tmd Test

duration

x x number 0.1-99.9: 4 hours

br1,cev

End cell voltage

x x number 1.5-2.0:1.85V/cell

br1,btv

Battery test rectifier voltage

x x number 42-52:42V

Highest Battery Temperature: When requested, will show the hottest temperature

monitored by the VT-Probes.

Total Battery Current: When requested, will display the current being drawn by the

battery string. This is determined by subtracting the load current from the total

rectifier output current.

Plant Battery Test: When initiated, this function lowers the plant voltage to 44V and

allows the batteries to discharge into the load. This may be used to determine the

health of the batteries.

Voltage Imbalance Detection Enable: Activates the Shorted Cell Detection alarm.

Number of Temperatures Present: When requested, will display the number of

QS873A (VT-Probes) that are currently connected to the system.

Number of mid-Cell V Present: When requested, will display the number of

ES771A (Remote Voltage Monitoring Modules) that are currently connected to the

system.