CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

21

Output Noise, Ripple

250 millivolts peak to peak maximum, over the
range dc to 100 MHz

Load Share Accuracy

1.5A maximum deviation between rectifiers

Heat Dissipation (per rectifier, full load)

177W (604 BTU) at 100 to 120 Vac operation
212W (724 BTU) at 200 to 240 Vac operation

Power Factor

>0.98 for loads > 50% full load

Selective High-Voltage Shutdown

Above 58 Vdc

Backup High-Voltage Shutdown

Above 60 Vdc for 1 millisecond

Table 2-H: QS864A Rectifier Specifications (Preliminary)

Nominal Output Voltage

48/52/54.5 Vdc

Operating Output Voltage Ranges

42 to 58 Vdc

Boost Voltage

48 to 58 Vdc

Output Current

0 to 40A at 54.5V

Nominal Input Voltage

200/208/240 Vac

Input Voltage Ranges

150 to 275 Vac

Input Current

11.8A at 208 Vac

Operating Frequency Range

45 to 66 Hz

Operating Temperature

-40 to +75 °C

Output Voltage Regulation

±0.5%

Output Noise, Ripple

250 millivolts peak to peak maximum, over the
range dc to 100 MHz

Load Share Accuracy

1.5A maximum deviation between rectifiers

Heat Dissipation (per rectifier, full load)

240W (819 BTU) at 240 Vac operation

Power Factor

>0.98 for loads > 50% full load

Selective High-Voltage Shutdown

Above 58 Vdc

Backup High-Voltage Shutdown

Above 60 Vdc for 1 millisecond

Table 2-I: QS865A Rectifier Specifications

Nominal Output Voltage

48/52/54.5 Vdc

Operating Output Voltage Ranges

42 to 58 Vdc

Boost Voltage

48 to 58 Vdc

Output Current

0 to 50A at 54.5V

Nominal Input Voltage

200/208/240 Vac

Input Voltage Ranges

150 to 275 Vac

Input Current

14.5A at 208 Vac

Operating Frequency Range

45 to 66 Hz

Operating Temperature

-40 to +65 °C

Output Voltage Regulation

±0.5%

Output Noise, Ripple

250 millivolts peak to peak maximum, over the
range dc to 100 MHz

Load Share Accuracy

1.5A maximum deviation between rectifiers

Heat Dissipation (per rectifier, full load)

267W (911 BTU) at 240 Vac operation

Power Factor

>0.98 for loads > 50% full load

Selective High-Voltage Shutdown

Above 58 Vdc

Backup High-Voltage Shutdown

Above 60 Vdc for 1 millisecond